Design

ASR A3.4: Workplace lighting.
What employers must comply with.

The German Technical Rule for Workplaces ASR A3.4 "Lighting and visual contact" sets out the minimum lighting levels for workplaces, warehouses and traffic routes in Germany. Anyone who complies with it can assume that they meet the Workplaces Ordinance (ArbStättV). Here you will find the most important minimum values, the requirements beyond brightness alone and the difference from DIN EN 12464-1.

Updated on · 6 min read · TRiALED lighting advice

At a glance
  • The relevant version is the May 2023 edition – since then, the rule has been called "Lighting and visual contact" and also covers safety lighting
  • Anyone who complies with the ASR can assume that they meet the requirements of the Workplaces Ordinance
  • Minimum values, for example: office work 500 lx, shipping and packing 300 lx, warehouses with search tasks 100 lx, loading ramps 150 lx
  • The average illuminance must not fall below the minimum value during operation – not even after years

What is ASR A3.4?

The Technical Rules for Workplaces (ASR) put into concrete terms the Workplaces Ordinance. ASR A3.4 covers lighting and, since the May 2023 edition, also visual contact with the outside. It gives concrete form to § 3a (1) and Annex No. 3.4 of the ordinance. With this edition, safety lighting has also moved into the rule; the former ASR A3.4/7 has been withdrawn.

An important point is the so-called presumption of conformity under § 3a ArbStättV: anyone who complies with the rule can assume that the requirements of the ordinance are met. Anyone who chooses a different solution must achieve at least the same level of safety and health protection.

Minimum values: the key values from Annex 3

For many work rooms, workplaces and activities, Annex 3 of the ASR specifies a minimum value for average illuminance and a minimum value for colour rendering Ra. A selection:

Area or activityMinimum illuminanceMinimum Ra
Office: writing, reading, data processing500 lx80
Office: filing, copying300 lx80
Storage with uniform or bulky stored goods50 lx60
Storage with search tasks for non-uniform stored goods100 lx60
Storage with reading tasks200 lx60
Shipping and packing areas300 lx60
Loading ramps and loading areas150 lx40
Corridors without vehicle traffic50 lx40
Corridors with vehicle traffic150 lx40
Stairs, escalators, lifts100 lx40
Canteens, kitchenettes, break rooms200 lx80
Vehicle workshops300 lx80
Assembly in metalworking: rough / medium-fine / fine / very fine200 / 300 / 500 / 750 lx80
Assembly in the electrical industry: rough / medium-fine / fine / very fine300 / 500 / 750 / 1.000 lx80
Electronics workshops: testing, adjusting1.500 lx80

For office work, the rule also requires a vertical illuminance of at least 175 lx. The values apply to the reference surface of the respective visual task. If an activity is not listed in the table, the employer sets the value as part of the risk assessment. The full annex in its current version is always authoritative.

More than lux: uniformity, surroundings, glare

  • Minimum means minimum: The average illuminance must not fall below the value in Annex 3. This applies both when setting up and when operating the installation – including when luminaires age and get dirty over the years.
  • Uniformity: Within the workplace area, illuminance must not fall below 0.6 times the average illuminance at any point. The lowest value must not lie in the area of the main visual task.
  • Surrounding area: With 300 lx at the workplace, the surroundings need at least 200 lx; with 500 lx or more, at least 300 lx.
  • Glare: Disturbing glare must be minimised, and glare that creates a risk of accidents must be avoided. The ASR does not give a numerical value such as a UGR value.
  • Colour rendering: The Ra value of the luminaire must not be lower than the value in Annex 3.

ASR A3.4 or DIN EN 12464-1?

The two are often mentioned in the same breath, but they play different roles. DIN EN 12464-1 is a European standard for lighting design with maintained values, glare limits and other planning parameters for a very wide range of visual tasks. ASR A3.4 puts the German Workplaces Ordinance into concrete terms. It does not mention DIN EN 12464-1 and makes clear that standards used as a planning basis may differ from it, while the requirements of the ASR apply for occupational safety.

ASR A3.4DIN EN 12464-1
TypeTechnical rule under the Workplaces OrdinanceEuropean standard for lighting design
ValuesMinimum values that must not be undercut during operationMaintained values and other planning parameters
GlareGeneral requirement without a numerical valueLimit values as UGR
EffectPresumption of conformity under § 3a ArbStättVPlanning basis, no presumption of conformity of its own

In practice, you plan with both: the lighting calculation to DIN EN 12464-1 ensures good visual conditions, and the check against ASR A3.4 ensures that the minimum values for occupational safety are reliably met. Where the values differ, it is worth planning with the higher one.

Daylight and visual contact

  • The Workplaces Ordinance requires work rooms to have sufficient daylight wherever possible and a visual connection to the outside.
  • According to the ASR, daylight is considered sufficient if the daylight factor is above 2 % (above 4 % with roof lights) or the window area is at least one tenth of the floor area of the room.
  • For visual contact, the rule requires, among other things, colour-neutral glazing with Ra ≥ 90 and a total area of at least 1.25 m² for room depths up to 5 m, or 1.50 m² for deeper rooms.

This is a gain for artificial lighting design: where enough daylight comes in through windows and roof lights, daylight control dims the luminaires without the minimum values being undercut.

Measuring, testing, maintaining

  • Measuring instrument: at least class C to DIN 5035-6.
  • Measuring height: 0.75 m for seated and 0.85 m for standing work, on traffic routes no more than 0.20 m above the floor.
  • Maintenance: at the latest when the installation no longer meets the requirements of the ASR. The rule does not set a fixed interval.
  • After changes: If the workplace or the visual task changes, the lighting must be checked again.

In older installations with fluorescent or discharge lamps, the luminous flux falls over the years. A measurement can show that the minimum values are no longer reached – a good reason to combine the retrofit with a lighting calculation. What this looks like in practice is shown on our pages on LED retrofits in industry, LED retrofits in logistics and LED retrofits in the office.

LED savings calculatorWhat can your lighting save?Energy costs, CO₂ and payback in just a few minutes.Calculate the saving

Frequently asked questions

What does ASR A3.4 regulate?

The German Technical Rule for Workplaces ASR A3.4 "Lighting and visual contact" puts into concrete terms the requirements of the Workplaces Ordinance for daylight, visual contact with the outside, artificial lighting and safety lighting. Among other things, it sets minimum values for illuminance and colour rendering for work rooms and activities.

How many lux does an office workstation need under ASR A3.4?

At least 500 lx for writing, reading and data processing, with colour rendering of at least Ra 80, plus a vertical illuminance of at least 175 lx. For filing and copying, the rule specifies 300 lx.

How bright does a warehouse need to be under ASR A3.4?

That depends on the stored goods: at least 50 lx for uniform or bulky stored goods, 100 lx for search tasks and 200 lx for reading tasks. Shipping and packing areas need 300 lx, loading ramps 150 lx.

Is ASR A3.4 mandatory?

The ASR is not a law; it puts the Workplaces Ordinance into concrete terms. Anyone who complies with it can assume that they meet the ordinance. Anyone who deviates from it must achieve at least equivalent safety and health protection.

What is the difference between ASR A3.4 and DIN EN 12464-1?

DIN EN 12464-1 is a European planning standard with maintained values and glare limits. ASR A3.4 sets minimum values for occupational safety in Germany. It does not refer to the DIN standard and makes clear that its own requirements apply for occupational safety.

Which version of ASR A3.4 applies?

The May 2023 edition, published in the Joint Ministerial Gazette (GMBl 2023, p. 679). It replaced the 2011 version. Before planning, check whether any amendments have been published since.